Fire inspection readiness
Exit signs and emergency lighting: the restaurant checklist
Restaurants, bars and cafés are assembly occupancies, so the codes ask more of them than of a typical shop. What the dining room, kitchen and corridors need, how bright and how long emergency lighting must run, which tests you log, and what inspectors write up.
The short version
- Dining rooms with an occupant load of 60 or more and commercial kitchen food preparation areas need emergency lighting at an average of at least 10 lx, with no point below 1 lx 3.
- Exit signs are the green and white pictogram conforming to ISO 7010; internally lit electrical signs are built to CSA 22.2 No. 141 12.
- Most restaurant buildings fall in the 30-minute emergency power category 4, and Ontario fire services expect monthly tests and a yearly full-duration battery test, with records kept on site for at least two years 79.
- Your buying decision: after an inspection or before opening, decide whether to replace old red EXIT signs and tired battery units in one order, rather than patching unit by unit and failing the next re-inspection.
Every claim below links to the source it comes from. Where a figure is an estimate rather than a published number, this article says so.
A fire inspection order for a restaurant rarely says the building is unsafe. It says the occupant load card is missing, the kitchen exit is blocked with shelving, and there are no monthly emergency lighting test records 6. This checklist is the restaurant-specific companion to our guides on exit sign requirements in Ontario and emergency lighting testing under the Ontario Fire Code. Walk your dining room, kitchen and corridors with it before the inspector does.
Part one — what the codes require in a restaurant
1. Why restaurants get extra attention
Restaurants, bars and cafés are assembly occupancies under the Ontario Building Code. That matters for three reasons:
- Occupant load drives the rules. Dining, alcoholic beverage and cafeteria spaces are calculated at 1.10 m² per person 5. A 120 m² dining room is about 109 people before you count the bar.
- The 60-person threshold. Floor areas where the public congregates in Group A, Division 2 occupancies with an occupant load of 60 or more must have emergency lighting 3. Rooms with an occupant load over 60 in licensed beverage establishments with low lighting also need exit signs at their egress doorways 1.
- Kitchens are named outright. Food preparation areas in commercial kitchens are listed as a location that needs emergency lighting, regardless of seat count 3.
Code text cited from buildingcode.online is a third-party, unofficial reproduction of the pre-2024 code 13; your designer and fire prevention office are the final word.
2. Exit signs: the green running man
Where exit signs are required, every exit door gets one placed over or next to it 1. Triggers include a building more than two storeys high or a building with an occupant load over 150 1. Under the 2024 Building Code wording summarized by the City of Markham, the sign must:
- Be a green and white (or lightly tinted) graphical symbol 2.
- Conform to ISO 7010 for symbols E001 (exit left), E002 (exit right), E005 (90-degree arrow) and E006 (45-degree arrow) 2.
- If internally lit by an electrical circuit, be continuously illuminated and built to CSA 22.2 No. 141, Emergency Lighting Equipment 2.
- If photoluminescent, conform to CAN/ULC-S572 and stay visible after a power failure for the emergency lighting duration 2.
Where no exit is visible from a corridor used by the public, the sign needs an arrow showing the direction of travel 1. Circuits feeding illuminated signs must serve only emergency lighting and be connected to the emergency power supply 1.
Whether an old red EXIT sign must be swapped depends on your permit scope; any replacement should be the pictogram type.
3. Emergency lighting by area: how bright and how long
Emergency lighting must provide an average of not less than 10 lx at floor or tread level in the required locations, and the minimum at any point cannot drop below 1 lx 3. Emergency power must last 30 minutes for any building that is not in one of the longer-duration categories (such as high buildings, which need 2 hours) 4.
| Area | What the code text says | What to check |
|---|---|---|
| Dining room, bar, lounge | Emergency lighting at 10 lx average where the occupant load is 60 or more 3 | No dark corners behind booths; heads aimed at aisles, not walls |
| Kitchen (food preparation) | Emergency lighting at 10 lx average 3; normal lighting at least 500 lx 11 | A unit that lights the line and the route to the back door |
| Exits and corridors used by the public | 10 lx average emergency lighting 3 | Corridor to washrooms and the rear exit both covered |
| Washrooms | Not listed by name in 3.2.7.3 3; normal lighting at least 300 lx in sanitary facilities 11 | Ask your fire prevention office; many designers add a unit anyway |
| Service rooms | Principal routes to exits in service rooms need emergency lighting 3 | Electrical or mechanical room route lit |
Patios are not addressed directly in the code text we reviewed. If your patio's only way out runs through the building or along a side passage, ask the fire prevention office how they want it lit and signed.
4. The occupant load card
Inspectors check that the occupant load is posted. A Hamilton fire inspection order for a restaurant cited Ontario Fire Code Division B 2.7.1.5.(1) because no card was posted, quoting that "the occupant load shall be posted in a conspicuous location" 6. Some fire departments prepare the card themselves; in that case the department noted it was preparing a new one 6.
Where a floor area is designed for an occupant load other than the one from the Building Code table, a permanent sign stating that load must be posted in a conspicuous location 5. Designed loads in dining and beverage spaces cannot exceed what 0.6 m² per person produces 5. Adding seats after opening can make the posted number wrong.
Get this sourced
5. Get this sourced
Ridgeport Supply Co. sources exit signs, battery emergency lighting units, remote heads and photoluminescent signs from overseas manufacturers for Canadian restaurants and institutions, from Southwestern Ontario. Request a quote and send us the product, quantity, the standard required (for example ISO 7010 pictogram, CSA 22.2 No. 141 or CAN/ULC-S572), and your delivery location and date. Your electrician or fire protection contractor handles installation and sign-off.
Part two — the inspection-readiness checklist
6. Daily, monthly and annual tasks
Ontario fire services publish owner schedules drawn from the Fire Code. The core items for exit signs and emergency lighting:
| When | Task | Who |
|---|---|---|
| Daily | Check exit signs are clean and legible, and exit lights are lit and in good repair (2.7.3.1, 2.7.3.2) 7 | Opening manager |
| Monthly | Inspect and test emergency lighting systems, batteries, units and lamps (2.7.3.3) 7 | Trained staff or a fire protection contractor 10 |
| Yearly | Test battery-powered emergency lighting to confirm it stays on for at least 30 minutes 9 | Qualified fire protection contractor 10 |
| Yearly | Annual exit sign inspection 10 | Qualified fire protection contractor 10 |
Monthly routine: before service, press each unit's test button, confirm every head lights, and log the result the same day.
7. Records the inspector will ask for
The most common written-up item in a restaurant is not a broken light but a missing logbook. The Hamilton order cited the absence of monthly emergency lighting test records, alongside missing extinguisher and fire alarm records 6.
- A written record of each test and corrective measure, noting what was done and the date and time 8.
- Records retained for at least two years after being prepared 78.
- The original or a copy kept at the building, including the most recent and the immediately preceding record of each test 6.
- Initial verification reports for fire protection systems installed after November 21, 2007 kept for the life of the system 7.
8. What an inspection order looks like, and the fines
When an inspector finds a contravention, they issue an order or inspection report identifying it, with a deadline to fix it 8. The Hamilton restaurant order listed eight items, including blocked exit routes in the kitchen and missing records, with a compliance date about six weeks after service, and warned that re-inspection fees may apply if work is not finished 6. A request for review by the Fire Marshal had to be received within 15 calendar days of service 6.
Penalties can be pursued under the Provincial Offences Act. The City of Barrie states that a person or a director of a corporation can be liable to a fine of up to $50,000, and a corporation up to $100,000 8.
Quick pre-inspection walk
9. Replacing failed units and old signs
Emergency lighting batteries are covered by the monthly inspection and test 7, and battery units must hold for the full duration in the yearly test 9. A unit that fails the yearly test needs a new battery or a new unit before the next inspection. Units of the same age tend to fail together, so replacing the set at once keeps your log simple.
- Match the replacement's rated duration to the 30-minute or longer requirement for your building 4.
- For new exit signs, buy ISO 7010 green pictograms with the arrow variants you need 2.
- For photoluminescent signs, confirm CAN/ULC-S572 and that your normal lighting charges them 2.
- Have a licensed electrician install anything hard-wired, and log the change.
10. What to send us for a quote
- Count of exit signs by type: single-face, double-face, left, right, 45-degree or 90-degree arrow.
- Sign technology: LED internally illuminated (CSA 22.2 No. 141) or photoluminescent (CAN/ULC-S572).
- Count of battery emergency units and remote heads, with voltage and the run-time your designer specifies.
- Mounting: wall, ceiling or end; indoor or damp location such as near a dish pit or patio door.
- Any inspection order or contractor deficiency list you are working from.
- Delivery address in Ontario and the date of your re-inspection or opening.
Request a quote or read how our sourcing works. Opening a new location? See the restaurant opening supplies checklist.
Institutional supply
Supplying a school, office or facility?
We source and supply first aid kits, safety signage, air purifiers and facility products for Ontario institutions, quoted delivered in Canadian dollars. See institutional supply.
Request a quoteBuying regularly?
Open a wholesale account
Trade pricing, the full product catalogue and live status on every request and order.
Apply to buyCommon questions
Does a restaurant in Ontario need emergency lighting in the dining room?
Yes, where the dining floor area has an occupant load of 60 or more. The Building Code requires emergency lighting at an average of at least 10 lx in floor areas where the public congregates in Group A, Division 2 occupancies with an occupant load of 60 or more 3.
Are red EXIT signs still allowed in Ontario restaurants?
Required exit signs under the current Building Code wording are green and white graphical symbols conforming to ISO 7010 2. Whether an existing red sign must be replaced depends on your permit and renovation scope, so confirm with your building department, and buy the pictogram type for any replacement.
How long must restaurant emergency lights stay on?
How long do I keep emergency lighting test records?
Sources
Every figure and rule above comes from one of these. Where this article draws a conclusion the source does not state literally, or gives an estimate rather than a published number, it says so in the text.
- buildingcode.online (third-party reproduction) — Ontario Building Code 3.4.5.1, Exit Signage
- City of Markham Building Standards — Builder Tip No. 85, Visibility and Illumination of Exit Signs (2024 OBC)
- buildingcode.online (third-party reproduction) — Ontario Building Code 3.2.7.3, Emergency Lighting
- buildingcode.online (third-party reproduction) — Ontario Building Code 3.2.7.4, Emergency Power for Lighting
- City of Ottawa, Ottawa Fire Services — Occupant load
- City of Hamilton Fire Department — Fire Code inspection order for a restaurant (August 2024)
- Windsor Fire & Rescue Services — Owner Fire Code inspection and testing information
- City of Barrie — Business Owner Fire Safety Responsibilities
- Oro-Medonte Fire & Emergency Services — Fire Code Compliance for Oro-Medonte Businesses
- Town of Georgina Fire and Rescue Services — Fire Code for Business Owners and Operators
- buildingcode.online (third-party reproduction) — Ontario Building Code 3.2.7.1, Minimum Lighting Requirements
Last reviewed November 22, 2026. Rules and rates change. If you find something here that has gone out of date, tell us and we will fix it. This guide is general information, not legal or customs advice.