Emergency lighting testing in Ontario: monthly and annual Fire Code checks, records and replacement units
What O. Reg. 213/07 expects from schools, long-term care homes, municipal buildings and offices, what changed in 2026, and how to replace failed battery units without a second deficiency.
The short version
- Test monthly, run a full-duration test yearly. Ontario fire services describe a monthly function check of every battery unit and an annual test that runs the lights for their full design duration under simulated power failure 25.
- The 2026 Fire Code moved the detail. Since O. Reg. 87/25 took effect on January 1, 2026, Article 2.7.3.3 says emergency lighting must be maintained in operating condition in conformance with Section 6.7 13.
- Records are not optional. Every test needs a written record of what was done and when, kept at the building for the Chief Fire Official for at least two years 17.
- Your decision: repair the battery or replace the unit. When a unit fails its annual duration test, you choose between a replacement battery and a new approved unit or combination exit unit, and the approval mark is not negotiable in Ontario 811.
Every claim below links to the source it comes from. Where a figure is an estimate rather than a published number, this article says so.
Emergency lighting testing in Ontario comes down to two routines and a logbook: a quick monthly check that every battery unit switches on when normal power fails, and an annual test that proves each unit lasts its full design duration. This guide covers what the Ontario Fire Code (O. Reg. 213/07) asks of schools, long-term care homes, municipal buildings and offices, what changed in 2026, record keeping, common deficiencies and buying replacement units.
Part one — The rules and the routine
1. What the Ontario Fire Code says about emergency lighting
Article 2.7.3.3 now reads: emergency lighting and exit signs shall be maintained in operating condition in conformance with Section 6.7 1. That wording arrived with O. Reg. 87/25, which the Office of the Fire Marshal says aligns the Ontario Fire Code more closely with the 2020 National Fire Code and came into force on January 1, 2026, with a few exceptions 3.
Before 2026, the same article spelled the routine out directly. As presented by the Office of the Fire Marshal, Sentence 2.7.3.3(3) required unit equipment to be tested monthly to ensure the lights function on failure of the primary power supply, and annually to ensure each unit provides emergency lighting for a duration equal to the design criteria under simulated power failure conditions 2. Municipal fire services continue to publish that monthly and annual cadence for owners 56.
Where a building has a generator rather than battery units, Section 6.7 has long required the emergency power system to be inspected, tested and maintained in conformance with CSA C282, with hospital essential electrical systems following CSA Z32 4.
Exit signs are covered by the same article. For sign types, placement and the pictogram rules, see our guide to exit sign requirements in Ontario; this guide stays on testing and replacement.
2. Monthly and annual emergency lighting testing in Ontario
Monthly emergency light test
Georgina Fire and Rescue Services tells owners that emergency lights must be tested monthly, by switching off the breaker or pressing the unit's test button, for 30 seconds to confirm the units operate properly 5. Barrie's maintenance schedule lists the monthly task as inspecting and testing emergency lighting systems, batteries, units and lamps 6. Inspection records also check pilot lights, terminals, clamps and the battery surface 8.
Annual duration test
Once a year, each unit runs under simulated power failure for its full design duration 2. Georgina says the annual inspection must be done by a qualified fire protection contractor 5. A complete annual record captures start and end battery voltage, load test minutes, AC power-on voltage and whether the charger is functioning to the manufacturer's specifications 8. Forms based on the National Fire Code also check electrolyte level and specific gravity on wet-cell batteries and the charging voltage, current and recovery period after the duration test 9.
| Test | How often | What is checked | Who usually does it |
|---|---|---|---|
| Function test | Monthly | Unit switches to battery on power failure; lamps light 25 | Trained staff or contractor 5 |
| Visual inspection | Monthly | Pilot light, terminals, clamps, clean dry battery 8 | Trained staff or contractor |
| Duration test | Annually | Full design duration under simulated power failure 2 | Qualified fire protection contractor 5 |
| Charger check | Annually, after duration test | Charging voltage, current, recovery period 89 | Qualified contractor |
3. Design duration and light levels
The annual test is only meaningful if you know the design duration. Forms used by fire protection technicians offer three settings: 30 minutes, 1 hour or 2 hours 9. An Ontario engineering firm summarizes the Building Code as 30 minutes for most buildings, 1 hour for certain listed occupancies, and 2 hours for high buildings, with exit corridors and stairways needing an average of 10 lux and a minimum of 1 lux at floor level 12.
The Fire Code's retrofit sections give the same picture for existing buildings. In care occupancies and retirement homes, emergency lighting in exit stairways, public corridors and principal access to exits must last at least 30 min at an average of at least 10 lx at floor or tread level 4. In existing residential buildings higher than six storeys, the duration rises to 2 h where the highest floor is more than 18 m above grade 4.
4. Record keeping for emergency lighting tests
Subsection 1.1.2 of the Fire Code requires a record noting what was done and the date and time it was done 1. Records stay at the building for the Chief Fire Official, the current and immediately preceding reports must be available, and records are kept for at least two years after being prepared 7.
Georgina accepts a spreadsheet, a fire logbook or its Battery Powered Emergency Light Maintenance Record template for monthly tests 5. Whatever format you use, number every unit on a floor plan so a failed unit can be found and its history read in one line.
5. Typical emergency lighting deficiencies
The items on fire service inspection records point to what fails most often 89. Plan for these on every annual report:
- Unit does not transfer to battery, or one lamp head stays dark.
- Battery runs short of the design duration on the annual test.
- Pilot light out, so nobody can tell whether the unit is charging.
- Corroded or loose terminals and clamps, or a wet or dirty battery surface.
- Charger not recovering the battery within the manufacturer's specification.
- No monthly entries in the logbook, which is itself a deficiency because the Code requires a record 1.
Part two — Replacement and procurement
6. Get this sourced
Ridgeport Supply Co. sources emergency lighting battery units, remote heads, replacement batteries and combination exit units from overseas manufacturers. We check the CSA C22.2 No. 141 certification, the approval mark recognized in Ontario, battery type and rated duration, voltage and the bilingual labels against your requirement before you commit, and quote delivered in Canadian dollars. Request a quote and send the product, quantity, specs or standard required, delivery location and date.
7. Buying replacement battery units and combo exit units
CSA C22.2 No. 141 is the Canadian standard for emergency lighting equipment, covering exit signs, unit equipment, emergency luminaires and central power systems on circuits of 600 V or less 10. The Fire Code cites it alongside CSA C282 for emergency lighting power in its retrofit provisions 14. In Ontario, the Electrical Safety Authority says an electrical product must be approved, and carry the official mark of an accredited certification or evaluation agency, before it is used, sold, displayed or advertised for sale; installing unapproved equipment can lead to prosecution 11. Component marks are not accepted on complete end-use products 11.
Battery replacement or full unit replacement
Replace the battery when the unit body, charger and lamps pass and only the duration falls short. Replace the whole unit when the charger fails or the housing is damaged. Match battery chemistry, voltage and capacity to the unit's rating label.
Specify by building type
- Schools: tamper-resistant housings in gyms and corridors, and enough capacity for remote heads in large assembly rooms.
- Long-term care homes: confirm the design duration for the care occupancy and whether lighting is fed from a CSA Z32 essential electrical system 4.
- Municipal buildings: standardize on one unit family so spares fit everywhere.
- Offices: combination exit units cut the number of devices to test where the sign and the light serve the same exit.
8. Worked example: a 40-unit school
Take a two-storey school, under 18 m, with 40 battery units and a 30-minute design duration 412. Monthly, a custodian tests each unit for 30 seconds 5, logs pass or fail by unit number, and checks pilot lights and terminals 8. Two years of retention means 24 monthly sheets and two annual reports on site 7.
At the annual test the contractor runs all 40 units for 30 minutes and records start and end battery voltage 8. Six units fall short. Four have sound chargers and housings, so they get matched replacement batteries. Two have chargers that do not recover, so they are replaced with approved units carrying a recognized mark 11. The purchase order lists the CSA C22.2 No. 141 certification 10, the 30-minute rating, voltage and lamp head count, and the contractor retests the six units and records the result 1.
9. What to send us for a quote
- Product type: battery unit, remote heads, replacement batteries or combination exit unit.
- Quantity per building, and photos of the current units and their rating labels.
- Required design duration (30 minutes, 1 hour or 2 hours) and system voltage.
- Certification required: CSA C22.2 No. 141 and an approval mark recognized in Ontario.
- Battery chemistry and capacity if you are replacing batteries only.
- Building type and any housing needs (tamper-resistant, damp location).
- Delivery address and the date the annual report deficiencies must be closed.
Request a quote with these details, or read how Ridgeport sources for institutions first.
Institutional supply
Supplying a school, office or facility?
We source and supply first aid kits, safety signage, air purifiers and facility products for Ontario institutions, quoted delivered in Canadian dollars. See institutional supply.
Request a quoteBuying regularly?
Open a wholesale account
Trade pricing, the full product catalogue and live status on every request and order.
Apply to buyCommon questions
How often do emergency lights need to be tested in Ontario?
Emergency lights in Ontario are tested monthly and annually. The monthly test confirms each unit switches to battery when normal power fails, and Georgina Fire and Rescue Services describes a 30-second test. The annual test runs each unit for its full design duration under simulated power failure 25.
Who can do emergency lighting testing in Ontario?
For emergency lighting testing in Ontario, trained building staff or a contractor commonly do the monthly function test, while municipal fire services such as Georgina say the annual inspection must be done by a qualified fire protection contractor 5.
How long must emergency lights stay on during the annual test?
How long do you keep emergency light test records in Ontario?
What did the 2026 Ontario Fire Code change for emergency lighting?
Do replacement emergency lights need CSA approval in Ontario?
Sources
Every figure and rule above comes from one of these. Where this article draws a conclusion the source does not state literally, or gives an estimate rather than a published number, it says so in the text.
- O. Reg. 213/07: Fire Code — Government of Ontario (e-Laws)
- Fire Safety for Condominium Managers webinar slides (Office of the Fire Marshal presenter) — CMRAO
- Communiqué 2025-02: Ontario Regulation 87/25 amending the Fire Code — Office of the Fire Marshal (via OAFC)
- 2015 Fire Code Compendium, revised to February 1, 2020 — Publications Ontario
- Fire Code for Business Owners and Operators — Town of Georgina Fire and Rescue Services
- Fire Safety Maintenance Schedule — Barrie Fire and Emergency Service
- Important Ontario Fire Code Information for Building Owners — Windsor Fire and Rescue Services
- Annual Emergency Unit Lighting Inspection Record — City of Winnipeg Fire Prevention
- Unit Emergency Lighting Test and Inspection Record (National Fire Code basis) — firetechs.net
- CSA C22.2 No. 141-15, Emergency lighting equipment — Canadian Standards Referenced in Codes (NRC)
- Recognized Approval Marks — Electrical Safety Authority
- Emergency and Exit Lighting: OBC and CEC requirements — ETEM Engineering
Last reviewed November 18, 2026. Rules and rates change. If you find something here that has gone out of date, tell us and we will fix it. This guide is general information, not legal or customs advice.