Life safety

Exit sign requirements in Ontario: photoluminescent or LED

The Ontario Building Code requires the green running-figure pictogram, and it accepts two very different ways of keeping that sign visible when the power fails. Where signs are required, the standard each type must meet, the charging-light rules that catch out photoluminescent signs, and how to choose between the two.

Updated November 4, 2026Reading time about 9 minWritten for Facility managers, property managers, school boards and contractors in Ontario

The short version

  1. Required when an exit serves a building over two storeys, an occupant load over 150, or a room or floor area that relies on a fire escape 1.
  2. The sign is a green pictogram with a white symbol, sized to ISO 7010 symbols E001, E002, E005 and E006 1.
  3. Electrically lit signs must conform to CSA C22.2 No. 141. Photoluminescent signs must conform to CAN/ULC-S572 and carry a label stating their tested duration 1.
  4. A photoluminescent sign is only as good as its charging light: continuously on, not on a switch, timer or motion sensor, at the light level the sign's listing requires 23.

Every claim below links to the source it comes from. Where a figure is an estimate rather than a published number, this article says so.

Exit signs are one of the few building products where the code tells you both what the sign must look like and how it must stay lit. That makes them a good fit for a planned replacement program, and an easy fail on a fire inspection if the wrong type goes up. This guide works from the Ontario Building Code's exit sign article (Division B, 3.4.5.1) and two published inspection checklists for photoluminescent signs.

Part one — what the code requires

1. Where exit signs are required

Under Article 3.4.5.1, every exit door needs a sign over it or next to it when the exit serves any of the following 1:

  • a building more than two storeys high,
  • a building with an occupant load over 150, or
  • a room or floor area that has a fire escape as part of its required means of egress.

Signs are also needed at egress doorways from rooms holding more than 60 people in assembly occupancies such as theatres and dance halls, at exits serving hotels, and wherever the low lighting of a space calls for them 1.

Where an exit is not visible from a public corridor or a principal route through an open floor area with more than 150 occupants, add a directional sign with an arrow pointing the way 1.

2. The look: green pictogram, white symbol

The code calls for a green pictogram with a white graphic symbol that meets the visibility rules of ISO 3864-1, sized to the ISO 7010 symbols 1:

ISO 7010 symbolUse
E001Emergency exit, left
E002Emergency exit, right
E005Directional arrow, 90°
E006Directional arrow, 45°

This is the "running man" sign. Red EXIT lettering does not meet the pictogram requirement. Whether older red signs in an existing building have to be replaced is a question for your local building or fire official. A renovation is the natural time to change them.

3. Keeping it lit: the two compliant routes

A sign has to stay visible when the power fails. The code allows two routes 1:

  • Internally lit (LED) signs must be continuously illuminated and, if electrically powered, conform to CSA C22.2 No. 141, Emergency Lighting Equipment. The circuit feeding them can only serve emergency lighting in that area, and it must connect to an emergency power supply.
  • Photoluminescent and self-luminous signs must conform to CAN/ULC-S572 and be labelled with the duration they were tested and listed for. That duration must meet the building's emergency lighting duration under Clause 3.2.7.4.(1)(b).

Part two — photoluminescent signs in practice

4. The charging light is part of the sign

A photoluminescent sign stores light from the room and gives it back in a blackout. Inspectors therefore check the light source as closely as the sign. Published checklists from Alberta and Winnipeg agree on the essentials 23:

  • The sign must be continuously lit by normal building light so it stays charged.
  • The charging light cannot be on a switch, timer, motion sensor, dimmer or building automation schedule. Breakers are locked on, or only authorized staff can reach them.
  • The light type and level must match the sign's listing. Winnipeg's checklist uses a minimum of 54 lux on each sign face.
  • The sign must be within the maximum viewing distance printed on its label.

Alberta's code interpretation adds that, under those conditions, the charging lights do not need to be on emergency power 2. Ask your Ontario building official to confirm the same for your project. It is the main reason photoluminescent signs cost less to install.

5. Photoluminescent or LED: how to choose

Photoluminescent (CAN/ULC-S572)LED (CSA C22.2 No. 141)
WiringNone at the signEmergency circuit or battery unit
Energy useZeroSmall, continuous
MaintenanceKeep the charging light on and the face cleanBattery and lamp checks, scheduled tests
Works inCorridors and rooms that stay lit while occupiedAny space, including dark rooms and dimmed venues
Main riskCharging light switched off or too dimBattery failure found only at a test

For schools and offices with corridors lit all day, photoluminescent signs usually cost less over their life. For auditoriums, gyms with dimmed lighting, or rooms where lights go off when empty, choose LED signs on emergency power.

6. Inspection and testing

For battery-powered emergency units, the National Fire Code calls for a monthly inspection and a monthly test that the unit switches on when power fails. It also requires a full-duration test at least every 12 months, with charging checks afterwards 4. Exit signs must stay lit whenever the building is occupied 4. Ontario's Fire Code sets the rules locally, so confirm the intervals with your fire department and keep written records of each check.

For photoluminescent signs, the routine check is simpler: confirm the charging light is on and the sign face is clean and undamaged.

7. What to ask for when you buy

  • The listing mark and standard on the sign: CAN/ULC-S572 for photoluminescent, CSA C22.2 No. 141 for lit units.
  • For photoluminescent signs: the rated duration, maximum viewing distance and required charging light level, in writing.
  • The ISO 7010 symbol you need (left, right, or with an arrow) for each location, taken from a walk-through.
  • Matching mounting hardware and a spare sign for every 20 or so installed.

Institutional supply

Supplying a school, office or facility?

We source and supply first aid kits, safety signage, air purifiers and facility products for Ontario institutions, quoted delivered in Canadian dollars. See institutional supply.

Request a quote

Buying regularly?

Open a wholesale account

Trade pricing, the full product catalogue and live status on every request and order.

Apply to buy

Common questions

Are red EXIT signs still allowed in Ontario?

The Ontario Building Code requires a green pictogram with a white symbol to ISO 7010 1. Whether existing red signs in an older building must be replaced depends on the building and any renovation work, so confirm with your local building or fire official.

Are photoluminescent exit signs legal in Ontario?

Yes. The Building Code allows photoluminescent signs that conform to CAN/ULC-S572 and are labelled with their tested duration, which must meet the building's emergency lighting duration 1.

How much light does a photoluminescent exit sign need?

Whatever the sign's listing specifies. Winnipeg's inspection checklist uses a minimum of 54 lux on each sign face, from a light that is not on a switch, timer or motion sensor 3.

Do photoluminescent exit signs need emergency power?

The sign itself doesn't. Alberta's code interpretation says its charging lights don't need emergency power either, provided they stay on continuously on a dedicated circuit that only authorized staff can control 2. Confirm this with your Ontario building official.

How often are emergency lights and exit signs tested?

Under the National Fire Code, battery units are inspected and tested monthly, with a full-duration test at least every 12 months 4. Confirm Ontario Fire Code intervals with your local fire department.

Sources

Every figure and rule above comes from one of these. Where this article draws a conclusion the source does not state literally, or gives an estimate rather than a published number, it says so in the text.

  1. Ontario Building Code, Division B, 3.4.5.1 Exit Signs (consolidated text, buildingcode.online)
  2. Government of Alberta — STANDATA 19-BCI-006, Photoluminescent exit signs
  3. City of Winnipeg — Photoluminescent Exit Signs Checklist
  4. Emergi-Lite (ABB) — Fire code requirements for emergency lighting (National Fire Code excerpts)

Last reviewed September 27, 2026. Rules and rates change. If you find something here that has gone out of date, tell us and we will fix it. This guide is general information, not legal or customs advice.