Facilities & safety

Fire door inspection in Ontario: what the Fire Code requires, what fails, and when to replace

Doors in fire separations must be inspected every month under the Ontario Fire Code. Here is what inspectors look for, how NFPA 80 fits in, and how to buy replacement doors and hardware that keep the rating.

Updated November 18, 2026Reading time about 9 minWritten for Facilities managers, custodial leads and purchasing officers at Ontario schools, long-term care homes, hospitals and municipal buildings.

The short version

  1. Inspect every month. Ontario fire services summarize the Fire Code (O. Reg. 213/07) as requiring all doors in fire separations to be inspected monthly, under Article 2.2.3.4 12.
  2. Wedges are the top failure. Fire-rated doors must not be wedged open and self-closing devices must be kept operable; any replacement door must meet or exceed the separation's rating 34.
  3. NFPA 80 sets the detailed checklist. The Ontario Building Code requires closures in required fire separations to be installed in conformance with NFPA 80, which calls for inspection after installation, after repairs and annually 58.
  4. Your decision: repair or replace. Holes, damaged labels and field modifications decide whether a door can be fixed in place or must be replaced with a labelled assembly of the same or higher rating 3910.

Every claim below links to the source it comes from. Where a figure is an estimate rather than a published number, this article says so.

Fire door inspection in Ontario is an ongoing owner duty, not a one-time building permit item. Once a school, long-term care home or municipal building is occupied, the Ontario Fire Code requires the doors in its fire separations to be inspected monthly, deficiencies to be corrected immediately, and records to be kept at the building for at least two years. This guide covers what that monthly check should include, how the NFPA 80 annual inspection criteria fit on top of it, the defects that most often fail an inspection, and how to decide between repairing a door and buying a replacement assembly.

Part one — What the rules require

1. The Fire Code rule: monthly fire door inspection

The Ontario Fire Code places responsibility on the building owner unless the Code says otherwise 1. Under the Fire Code, an owner means any person, firm or corporation having control over any portion of the building, so a tenant operator can carry duties too 11.

Municipal fire services publish maintenance schedules that summarize the Code. Windsor Fire & Rescue and Barrie Fire both list "inspect all doors in fire separations" as a monthly task, referencing Article 2.2.3.4, and both list checking that doors in fire separations are closed as an as-required task 12. Annual items in the same schedules include fire dampers and fire stop flaps 12.

When a defect is found in fire safety equipment, Windsor's summary states that corrective action must be taken immediately by the owner or the owner's authorized agent 1.

Records you must keep for fire door inspections

Barrie's schedule summarizes Division B, Article 1.1.2.2: a copy of any record required by the Code must be kept at the building it relates to for at least two years, and at least the most recent and the immediately preceding record of a given test or inspection must be retained 2. Tests and corrective measures need a written record of what was done and when 2. Fire prevention officers can enter at all reasonable times and may ask to see those records 11.

2. Fire door inspection in Ontario: what gets checked

Municipal inspection checklists focus on a short list of conditions 34:

  • The door is not wedged, propped or tied open.
  • The self-closing device is present and operable, and the door closes and latches on its own.
  • Penetrations or damage to the fire-rated wall or ceiling around the door are repaired to keep the separation intact.
  • Any replaced door meets or exceeds the rating of the fire separation it sits in.
  • Exit doors open in the direction of travel and open easily.

Industry guidance adds maintenance points: closures must be kept operable at all times, fusible links and heat- or smoke-actuated devices kept undamaged and free of paint, and door hardware adjusted so doors close and latch properly 13. Intumescent seals and edge strips wear in high-traffic corridors and lose effectiveness against smoke 13.

3. NFPA 80: the annual inspection checklist

The Ontario Building Code (Article 3.1.8.5) requires every door used as a closure in a required fire separation to be installed in conformance with NFPA 80, Fire Doors and Other Opening Protectives, and to carry labels or classification marks identifying the testing laboratory where a fire-protection rating is required 5. That is the reason NFPA 80 is the practical benchmark for what a compliant door looks like. The building code side of ratings is covered in our guide to fire-rated doors under the Ontario Building Code.

NFPA 80 calls for an inspection after installation, a reinspection after repairs or modifications, and annual inspections after that, with a unique record for each door assembly that lists the date, inspector and deficiencies 8. NFPA's own checklist for swinging doors with builders hardware (2019 edition) includes these points 7:

CheckPasses when
LabelsDoor and frame labels are present, visible and readable 7
Holes and breaksNo open holes or breaks in door or frame surfaces 7
GlazingVision lights and glazing beads are intact and secure 7
HardwareHardware is labelled for use on the door; no missing or broken parts 7
Gaps at head, jambs, meeting stilesUp to 1/8 in. for wood doors over 20 minutes; up to 3/16 in. for hollow metal doors 8
Gap under door (pull side)Not more than 3/4 in. (19 mm) 7
SignageCovers no more than 5% of the door, attached with adhesive, not screws 7
Closing and latchingDoor closes fully from full open and latches 7
Pairs with coordinatorInactive leaf closes before the active leaf 7
Field modificationsNone that void the label 8

NFPA recommends repeating the operational test three times 7.

4. Hold-open devices and magnetic releases

Doors that staff want open all day should be on a code-compliant hold-open device, never a wedge. The Ontario Building Code permits a hold-open device on a door in a required fire separation (other than an exit stair door in a building more than 3 storeys high, and certain vestibule doors) provided it releases the door on the required signals 6. Default release triggers are a sprinkler system, heat-actuated device, fusible link or smoke detector; where the building has a fire alarm system, release from that system is generally required 6. Hospitals and long-term care homes have specific rules for sleeping-room doors and paired doors 6.

During inspection, NFPA's checklist requires that an automatic-closing door becomes self-closing when the hold-open mechanism activates or loses power, tested on activation of the interconnected fire alarm devices where applicable 7. Coordinate that test with your fire alarm service visit.

Part two — Fixing and buying

5. Get this sourced

Ridgeport Supply Co. sources fire-rated doors, frames, closers and hold-open hardware from overseas manufacturers. We check fire-protection ratings, testing laboratory labels, hardware listings and test reports against your requirement before you commit, and quote delivered in Canadian dollars. Request a quote and send the product, quantity, specs or standard required, delivery location and date.

6. Repair or replace a failed fire door

Most failures are hardware: a closer out of adjustment, a latch that does not engage, a missing gasket. Those are repairs. The harder calls involve holes, labels and modifications.

Repairable

Holes left by removed hardware may be filled with steel fasteners that completely fill them or with the same material as the door or frame; the 2016 edition of NFPA 80 added listed filler material installed to the manufacturer's procedure 910. Job-site preparation for surface-applied hardware is allowed, and older editions cap field-drilled round holes at 1 inch in diameter 9.

Needs approval or relabelling

Anything beyond permitted job-site preparation, such as a rectangular cutout for an electric strike or trimming a door's width, is a field modification that needs advance permission from the listing laboratory through the manufacturer 9. Unapproved modifications can require relabelling by the lab, which means a site visit and can be costly 9. Covering an unapproved hole is not a repair 8.

Replace

Replace the assembly when the label is gone or illegible and cannot be restored, when damage goes beyond listed repair methods, or when the opening's rating has been raised by renovation. A replacement must meet or exceed the minimum rating of the separation 4.

7. Worked example: a 40-door school

A secondary school has 40 doors in fire separations. Monthly Fire Code inspections mean 480 door checks a year 1. Keeping records at the building for at least two years means roughly 24 monthly logs on file at any time 2. Adding one NFPA 80 annual inspection per door produces 40 unique door records each year 8.

Suppose the annual inspection finds a 45-minute wood door with a 3/16 in. gap at the latch jamb. For wood doors rated over 20 minutes the limit is 1/8 in., so it fails 8. If hinges and frame can be adjusted to close the gap, it is a repair; if the door was trimmed to fit, that is a field modification and the door likely needs replacement or relabelling 9.

8. What happens if you fail

A fire prevention officer who finds a violation issues an order or inspection report with a compliance deadline 11. Serious or repeated violations can lead to a ticket or summons under the Provincial Offences Act 11. Municipal fire services describe maximum fines of up to $50,000 for an individual, with possible imprisonment of up to one year, and up to $100,000 for a corporation 1112.

9. What to send us for a quote

  • Door count, sizes, swing and whether single or pair.
  • Required fire-protection rating for each opening (for example 20, 45 or 90 minutes).
  • Frame type and condition: replacing door only, or door and frame.
  • Hardware list: closer, latch or lockset, hinges, coordinator, gasketing, hold-open or magnetic release and fire alarm voltage.
  • Glazing or vision light requirements.
  • Copy of the inspection report or fire service order listing the deficiencies.
  • Delivery address, site access limits and required date.

Request a quote with these details, or read how Ridgeport sources for institutions first.

Institutional supply

Supplying a school, office or facility?

We source and supply first aid kits, safety signage, air purifiers and facility products for Ontario institutions, quoted delivered in Canadian dollars. See institutional supply.

Request a quote

Buying regularly?

Open a wholesale account

Trade pricing, the full product catalogue and live status on every request and order.

Apply to buy

Common questions

How often do fire doors need to be inspected in Ontario?

In Ontario, the Fire Code requires doors in fire separations to be inspected monthly, as summarized by municipal fire services referencing Article 2.2.3.4 12. NFPA 80, which the Ontario Building Code references for installation, also calls for a documented inspection of each fire door assembly annually and after any repair 58.

Can you prop open a fire door in Ontario?

No. Fire-rated doors in Ontario must not be wedged open, and their self-closing devices must be kept operable 34. A fire door can be held open only by a hold-open device that meets the Ontario Building Code and releases the door on a fire alarm, smoke detector, heat-actuated device or fusible link signal 6.

Who is responsible for fire door inspection in Ontario?

The building owner is responsible for fire door inspection under the Ontario Fire Code unless the Code states otherwise 1. The Fire Code defines owner broadly as any person, firm or corporation having control over any portion of the building, so tenants operating a space can also be accountable 11.

What causes a fire door to fail inspection?

A fire door usually fails inspection because it is wedged open, does not close and latch on its own, has a missing or painted-over label, has unapproved holes or modifications, or has gaps beyond NFPA 80 limits, such as more than 3/4 in. under the door 378.

How long do you keep fire door inspection records in Ontario?

Ontario Fire Code records, including fire door inspection records, must be kept at the building for at least two years, and at least the most recent and immediately preceding record of each inspection must be retained 2.

Sources

Every figure and rule above comes from one of these. Where this article draws a conclusion the source does not state literally, or gives an estimate rather than a published number, it says so in the text.

  1. Important Ontario Fire Code Information for Building Owners — Windsor Fire & Rescue Services
  2. Fire Safety Maintenance Schedule — Barrie Fire & Emergency Service
  3. Inspection Checklist — Brockville Fire Department
  4. Fire prevention, inspection & enforcement — City of Ottawa
  5. Installation of Closures, Article 3.1.8.5 (unofficial OBC text) — buildingcode.online
  6. Hold-Open Devices, Article 3.1.8.12 (unofficial OBC text) — buildingcode.online
  7. Inspection Checklist for Swinging Door with Builders Hardware — NFPA (hosted by South Carolina State Fire)
  8. From Signage to Latching Hardware: 13 Fire Door Inspection Criteria to Know — Buildings
  9. Decoded: Alterations to Fire Door Assemblies — iDigHardware
  10. Repairing Holes and Dents in Fire Doors — iDigHardware
  11. Business Owner Fire Safety Responsibilities — City of Barrie
  12. Fire Code Enforcement — City of Niagara Falls
  13. Fire safety: Building fire separation and closures — Ontario Construction News

Last reviewed November 18, 2026. Rules and rates change. If you find something here that has gone out of date, tell us and we will fix it. This guide is general information, not legal or customs advice.