Public-sector supply / Fire-rated openings

Fire-rated door requirements in Ontario: a buyer's guide

What the Building Code and Fire Code expect from a door in a fire separation, how to read the rating you need, and how to specify a complete, labelled assembly before you ask for prices.

Updated November 9, 2026Reading time about 10 minWritten for Facilities and procurement staff at Ontario schools, long-term care homes, hospitals, municipalities and property managers

The short version

  1. The closure rating follows the wall. The Building Code sets a minimum fire-protection rating for the door based on the required fire-resistance rating of the separation it sits in — a 1 h separation needs a 45 min closure, for example 1.
  2. Your buying decision is the assembly, not the slab. Door, frame, hinges, closer, latch and glazing are tested and labelled together, and the Code requires closures in fire separations to be installed to NFPA 80 16.
  3. Self-closing and positive latching are the default. Doors in fire separations need a self-closing device and swing doors need a positive latch, with a short list of exceptions 1.
  4. Owners inspect monthly and keep records. Ontario fire services summarize the Fire Code as requiring a monthly inspection of all doors in fire separations, with records kept for at least two years 34.

Every claim below links to the source it comes from. Where a figure is an estimate rather than a published number, this article says so.

A fire-rated door is a small part of a capital project and a large part of a fire inspector's checklist. When a school board, long-term care home, hospital or municipality replaces corridor or stair doors, the purchase has to match a rating set by the Ontario Building Code, arrive with labels the inspector can read, and stay compliant under the Fire Code for its whole life.

Part one — What the codes require

1. Which code applies to your doors

Two regulations govern fire-rated doors in Ontario.

  • The Building Code (the current edition is O. Reg. 163/24, published by the province in its 2024 Building Code compendium) decides what rating a new or replacement closure must have, installation and hardware 1.
  • The Fire Code (O. Reg. 213/07) applies once the building is occupied. It makes the owner responsible for inspecting and maintaining closures and for keeping records 34.

Older specifications and tender documents often still cite O. Reg. 332/12, the previous Building Code. Article numbers moved in the 2024 edition (the twenty-minute closure rule is now Article 3.1.8.12 1), so confirm the edition with your designer.

2. Separation rating vs. required closure rating

Article 3.1.8.4 says the fire-protection rating of a closure is determined by testing to CAN/ULC-S104 (doors), CAN/ULC-S106 or CAN/ULC-S112, and must conform to Table 3.1.8.4 for the required fire-resistance rating of the fire separation 1. The table reads:

Required fire-resistance rating of the fire separationMinimum fire-protection rating of the closure
30 min20 min
45 min45 min
1 h45 min
1.5 h1 h
2 h1.5 h
3 h2 h
4 h3 h

Source: Ontario 2024 Building Code compendium, Table 3.1.8.4 1.

When a 20 minute door is permitted

Article 3.1.8.12 lets a door assembly with a fire-protection rating of at least 20 min serve as the closure in a fire separation required to be no more than 1 h, located between a public corridor and a suite, a corridor and adjacent sleeping rooms, or a corridor and adjacent classrooms, offices and libraries in Group A, Division 2 occupancies; or in a separation of no more than 45 min in a building not more than 3 storeys high 1. Those doors must have clearances of not more than 6 mm at the bottom and 3 mm at the sides and top 1. In elementary and secondary schools, a door assembly conforming to Articles 9.10.13.2 and 9.10.13.3 may close a 30 min separation 1.

3. Closers, latches, hold-opens and glazing

  • Self-closing. Every door in a fire separation, other than doors to freight elevators and dumbwaiters, must have a self-closing device that returns it to the closed position 1. Exceptions exist for some classroom doors onto exit corridors in buildings of 3 storeys or less (hazardous classrooms excluded), some suite doors, and sleeping room doors in hospitals and long-term care homes within a compliant fire compartment 1.
  • Positive latching. Swing-type doors in fire separations need a positive latching mechanism that holds the door closed 1.
  • Hold-open devices. These are permitted on closures in required fire separations, but where there is a fire alarm system they must release on the alarm signal 1.
  • Wired glass. Fixed wired glass or glass block may protect openings in separations rated not more than 1 h, with a carve-out for the separation of exits 1.
  • Glass area and temperature rise. Table 3.1.8.17 limits glass area and temperature rise by location. A 45 min door between a dead-end corridor and the floor area is limited to 250 °C after 30 min and 0.0645 m² of wired glass or safety glazing in the door; exit enclosures in buildings of not more than 3 storeys have no temperature-rise limit and 0.8 m² of glass 1.

Lite size and glass type must fit both the Code table and the door's listing.

4. Get this sourced

Ridgeport sources labelled fire-rated door and frame assemblies from factories abroad, checks the certification paperwork against your schedule, and quotes delivered in Canadian dollars. Installation, field adjustments and final sign-off stay with your installer and the authority having jurisdiction. Request a quote with the product, quantity, the specification or standard required, the delivery location and the date you need it. If you buy through tenders, our guide to selling to the Ontario public sector explains how we fit your process.

Part two — Buying and keeping a compliant assembly

5. Why you buy the assembly, not just the slab

The Building Code requires every door used as a closure in a required fire separation to be installed in conformance with NFPA 80, Standard for Fire Doors and Other Opening Protectives, except as otherwise specified 1. Door frames have their own national standard: CAN/ULC-S105 covers frame assemblies for swinging fire doors tested for use with fire doors rated up to 3 hours under CAN/ULC-S104 2.

A rated slab in an unrated frame is not a rated opening. NFPA 80 inspection criteria flag field modifications that void the label and auxiliary hardware that stops the door closing or latching 7.

Checklist: what a compliant assembly includes

  • Door labelled with its fire-protection rating. Certification labels typically carry the certifier's mark, "listed fire door", manufacturer, product designation, rating, bolt throw and a serial number 6.
  • Frame labelled and built to CAN/ULC-S105 for the door's rating 2.
  • Hinges of the type and number in the listing; no missing or broken parts 7.
  • Closer that fully closes the door from the open position 7 and meets Article 3.1.8.13 1.
  • Positive latch that secures the door when closed 17, with bolt throw not less than the minimum shown on the label 6.
  • Hold-open or release device, if used, tied to the fire alarm 1.
  • Glazing that is rated, intact and within Table 3.1.8.17 area limits 17. Doors labelled to CAN/ULC-S104 with a temperature-rise rating state it on the label, for example 250 °C maximum where lites do not exceed 0.0645 m² 6.
  • Gasketing and edge seals where the listing requires them, including smoke and draft control gasketing 67.
  • Clearances within limits — 6 mm bottom and 3 mm sides and top for 20 min doors under the Code 1; NFPA 80 limits the bottom of a fire door to 3/4 inch 7.
  • Labels left legible — not painted over or removed 67.

6. Inspection and maintenance after handover

  • Monthly inspection. Barrie Fire and Emergency Service and Windsor Fire and Rescue both summarize Article 2.2.3.4 as requiring a monthly inspection of all doors in fire separations 34, plus routine checks that those doors are closed 34.
  • Fix defects immediately. When a defect is found in fire safety equipment, corrective action must be taken immediately 34. Damaged fire doors must be repaired or replaced to meet or exceed the required rating, fire doors are to remain closed, and door stops should be removed 8.
  • Keep records. A written record of what was done, with the date and time, must be kept at the building for at least two years 4.
  • NFPA 80 annual testing. NFPA 80 requires fire door assemblies to be inspected and tested not less than annually, with a written, signed record retained for the authority having jurisdiction 5.

7. Worked example: replacing corridor doors in a school wing

A school board is replacing doors in a two-storey elementary wing. The designer confirms the corridor-to-classroom walls are 1 h fire separations and the stair enclosures are also 1 h separations.

  1. Classroom doors (24 openings). Table 3.1.8.4 would call for 45 min in a 1 h separation, but Article 3.1.8.12 allows a 20 min door between a corridor and adjacent classrooms in a Group A, Division 2 occupancy where the separation is not required to exceed 1 h 1. Specify 20 min assemblies with bottom clearance of not more than 6 mm and 3 mm at sides and top 1. Confirm with the designer whether the classroom self-closer exception in Article 3.1.8.13 applies; hazardous classrooms such as labs still need closers 1.
  2. Stair doors (6 openings). No 20 min allowance applies, so Table 3.1.8.4 sets 45 min for the 1 h separation 1. For exit enclosures in buildings of not more than 3 storeys, Table 3.1.8.17 sets no temperature-rise limit and allows 0.8 m² of glass 1.
  3. Hardware. Positive latch on every swing door and alarm-released hold-opens on any stair door that must stay open 1.
  4. Paperwork. Ask for label details for every door and frame before production, and match them to the schedule on arrival.

To compare an overseas quote with a local one on equal terms, work out the delivered cost with our landed cost guide.

8. What to send us for a quote

  • Door schedule with opening numbers and locations
  • Sizes: door width, height and thickness, single or pair
  • Required fire-protection rating per opening, and the separation rating it sits in
  • Frame type: knock-down or welded, profile, wall type and throat
  • Hardware set per opening: hinges, closer, latch or lockset, exit device, hold-open
  • Glazing: lite size, glass type and any temperature-rise requirement
  • Finish: primed, factory-painted or veneer
  • Label requirements: certification mark and standards (CAN/ULC-S104, CAN/ULC-S105)
  • Quantities, including spares
  • Delivery location and the date you need it on site

Send it through Request a quote, and read how our sourcing works.

Institutional supply

Supplying a school, office or facility?

We source and supply first aid kits, safety signage, air purifiers and facility products for Ontario institutions, quoted delivered in Canadian dollars. See institutional supply.

Request a quote

Buying regularly?

Open a wholesale account

Trade pricing, the full product catalogue and live status on every request and order.

Apply to buy

Common questions

What fire rating does a door in a 1 hour fire separation need in Ontario?

Under Table 3.1.8.4 of the Building Code, a 1 h fire separation needs a closure with a fire-protection rating of at least 45 min, unless a specific allowance such as the 20 minute closure rule in Article 3.1.8.12 applies 1.

Can I use a 20 minute door on a classroom?

Article 3.1.8.12 permits a 20 min door assembly between a corridor and adjacent classrooms, offices and libraries in Group A, Division 2 occupancies where the separation is not required to exceed 1 h, with tight clearances of 6 mm at the bottom and 3 mm at the sides and top 1.

Do fire doors in Ontario have to be self-closing?

Yes, as a rule. Every door in a fire separation other than doors to freight elevators and dumbwaiters needs a self-closing device, with limited exceptions for some classroom, suite and hospital or long-term care sleeping room doors 1.

How often must fire doors be inspected?

Ontario fire services summarize the Fire Code as requiring a monthly inspection of all doors in fire separations 34. NFPA 80 also calls for inspection and testing of fire door assemblies not less than annually, with a signed record 5.

Does the frame need its own label?

Yes. Frames for swinging fire doors are covered by CAN/ULC-S105 2, and inspectors check that labels on the assembly are present and legible 7.

Who signs off a fire-rated door installation?

Your installer and the authority having jurisdiction. Ridgeport sources the product and checks certification paperwork and labels; installation to NFPA 80, which the Building Code requires 1, and final acceptance sit with them.

Sources

Every figure and rule above comes from one of these. Where this article draws a conclusion the source does not state literally, or gives an estimate rather than a published number, it says so in the text.

  1. Government of Ontario — 2024 Building Code compendium, Part 3: Fire protection, occupant safety and accessibility
  2. Standards Council of Canada — Standard Specification for Fire Door Frames Meeting the Performance Required by CAN/ULC-S104 (CAN/ULC-S105)
  3. Windsor Fire and Rescue Services — Owner Fire Code information
  4. Barrie Fire and Emergency Service — Fire Safety Maintenance Schedule
  5. UL — The Code Authority: Fire door inspections
  6. QAI Laboratories — FD001 Fire Door Labeling Guidelines
  7. Buildings — From signage to latching hardware: 13 fire door inspection criteria to know
  8. Township of Oro-Medonte Fire and Emergency Services — Fire safety brochure

Last reviewed November 9, 2026. Rules and rates change. If you find something here that has gone out of date, tell us and we will fix it. This guide is general information, not legal or customs advice.