Long-term care
HEPA air purifiers for long-term care homes in Ontario: how to spec, size and buy them
Portable air cleaners for resident rooms, dining rooms and outbreak wings. What the regulation and public health guidance actually say, how to size by CADR, and how to buy them cleanly.
The short version
- No rule mandates them: O. Reg. 246/22 requires working mechanical ventilation and HVAC inspected at least every six months; portable HEPA air cleaners are a supplement, not a substitute 51.
- Size by smoke CADR: Health Canada and PHO both use the rule that tobacco smoke CADR should be at least two-thirds of the room's floor area, assuming an 8-foot ceiling 32.
- Buy only approved, filter-only units: electrical products used in Ontario must carry a recognized certification mark, and ozone-producing or ionizing units should be avoided 72.
- The buying decision: whether to standardize one quiet room unit plus a high-CADR lounge unit across every home, with matched spare filters, or keep buying ad hoc when an outbreak hits.
Every claim below links to the source it comes from. Where a figure is an estimate rather than a published number, this article says so.
Ontario long-term care homes buy portable HEPA air cleaners as a supplement to the building's ventilation: there is no requirement to have them, but public health guidance supports them where ventilation is limited, and the home has to size, place and maintain them correctly. This guide covers what O. Reg. 246/22 and Public Health Ontario say, how to size units by CADR for resident rooms and lounges, noise and certification checks, filter replacement, and how a home's purchase should be run.
Part one — The rules and the sizing math
1. What Ontario rules apply to air in long-term care homes?
O. Reg. 246/22 under the Fixing Long-Term Care Act, 2021 does not mention portable air cleaners, but it sets the obligations they sit beside 5:
- s. 96(2)(c): HVAC systems are cleaned, in good repair and inspected at least every six months.
- s. 96(3): mechanical ventilation functions at all times, except on emergency generator power.
- s. 102: an IPAC program with a designated IPAC lead, an outbreak management system and a written outbreak response plan.
- ss. 23.1 and 24: air conditioning in every resident bedroom from May 15 to September 15, and a minimum of 22 degrees Celsius.
A portable air cleaner is not cooling equipment, but it competes with portable air conditioners for bedroom floor space and outlets, so plan both together.
Public Health Ontario's IPAC checklist for long-term care and retirement homes (March 2025) is the most direct provincial reference: indoor spaces should be as well-ventilated as possible with outdoor air, and portable or local air cleaners are considered to filter indoor air, especially where ventilation options are limited 6.
2. What do PHAC and Public Health Ontario say about portable HEPA air cleaners?
The Public Health Agency of Canada is careful about the evidence: it says there is no direct evidence that portable HEPA units reduce SARS-CoV-2 transmission in closed spaces, and that they do not replace ventilation, distancing and hygiene. It frames them as added protection where ventilation cannot be improved, in rooms that are not crowded 1. The practical rules are consistent:
- Run units continuously, intake clear of furniture and walls 1.
- Do not blow air directly at or between people 12.
- True HEPA removes at least 99.97% of particles at 0.3 µm; MERV 13 or higher is the stated alternative 2.
- Avoid ozone, UV and ion-generator units; use mechanical filtration only 21.
- Look for AHAM-certified CADR ratings 13.
Our schools HEPA guide covers classrooms. Long-term care differs: residents sleep in the room, units run around the clock, and outbreaks demand rapid redeployment.
3. How to size HEPA air purifiers for long-term care in Ontario
The two-thirds rule. Health Canada says tobacco smoke CADR should be at least two-thirds of the room's floor area in square feet; ratings assume an 8-foot ceiling, so higher ceilings need a unit rated for a larger room 3. PHO uses the same rule and suggests multiple units for larger areas 2.
The air changes formula. AHAM gives ACH = smoke CADR × 60 ÷ room volume (cfm and cubic feet). Its suggested room size works out to about 4.8 air changes per hour 4. None of the cited Canadian guidance sets a mandatory ACH target for long-term care.
Worked example
A 12 × 14 ft resident room with an 8 ft ceiling is 168 sq ft and 1,344 cu ft. Two-thirds of 168 gives a minimum smoke CADR of 112 3, and ACH = 112 × 60 ÷ 1,344 = 5.0 4. A 30 × 40 ft lounge with a 9 ft ceiling is 10,800 cu ft; because the ceiling exceeds 8 ft, size by volume: 5.0 × 10,800 ÷ 60 = 900 cfm, for example three 300 cfm units spread through the room 24.
| Space | Floor area | Volume | Smoke CADR | ACH |
|---|---|---|---|---|
| Private room, 8 ft ceiling | 168 sq ft | 1,344 cu ft | 112 cfm | 5.0 |
| Semi-private, 16 × 18 ft, 8 ft ceiling | 288 sq ft | 2,304 cu ft | 192 cfm | 5.0 |
| Lounge or dining, 9 ft ceiling | 1,200 sq ft | 10,800 cu ft | 900 cfm (3 × 300) | 5.0 |
Size at the fan speed the unit will actually run at night, not the top setting.
4. Get this sourced
Ridgeport sources portable HEPA air cleaners and matched replacement filters for Canadian long-term care and retirement homes, working directly with overseas manufacturers and landing goods under your specification. If you know what you need, request a quote and include the product, quantity, specs or standard required, delivery location and date. A request like "60 bedroom units, smoke CADR 120 or more, true HEPA, recognized Ontario approval mark, two spare filters each" is enough to price accurately the first time.
Part two — Specifying, running and buying them
5. Resident rooms: noise, placement and electrical approval
Noise is why units get switched off. PHO notes noise rises with fan speed, people turn units off to avoid it, and noise is rarely reported in a standard way 2; Health Canada advises a lower noise rating 3. In bedrooms, buy a unit that reaches the target CADR on a low setting. Keep it clear of walkers and transfer paths, never point the outlet at a bed 1, and in shared rooms avoid airflow running bed to bed 2.
Electrical approval is mandatory. The Electrical Safety Authority says an electrical product must be approved by an accredited certification or evaluation agency, and carry its mark, before it is used, sold or advertised in Ontario; connecting unapproved equipment is against the law 7. Recognized marks include CSA, ULC, UL, Intertek (ETL) and QPS; a component-only mark does not count on a finished product 7.
6. Dining rooms, lounges and outbreak use
Common areas need volume-based sizing and usually several units, spread out and aimed away from seated residents 12. Section 102 requires an outbreak management system and written response plan 5; write air cleaners into it:
- Hold a labelled, tested reserve that can move to an affected wing.
- Pre-assign priority rooms and lounges, sized from floor plans.
- Run portable HEPA units with HVAC and window ventilation before reoccupying a room 1.
- Keep a spare filter per reserve unit.
- Have the IPAC lead sign off on deployment 5.
Pair units with the rest of your outbreak stock; see our IPAC supplies guide for long-term care.
7. Filter replacement schedule and maintenance log
No cited Canadian source sets a fixed interval; PHAC, PHO and Health Canada all defer to the manufacturer 123, and PHO adds that the filter must fit its frame so air does not bypass it 2. That makes filter supply a procurement issue.
- Standardize on as few models as possible.
- Buy the first year of filters with the units.
- Tag each unit with an asset number, location and last change date.
- Log changes alongside the six-monthly HVAC inspection under s. 96 5.
For per-unit and per-filter costs after freight, duty and brokerage, see our landed cost guide for HEPA air purifiers.
8. How Ontario long-term care homes buy air cleaners
It depends on who operates the home. The Broader Public Sector Accountability Act, 2010 excludes a long-term care home from "publicly funded organization", so it is not caught by the $10 million test that designates other organizations 9; hospitals are designated 8. Where a purchase runs through a hospital or other designated organization, the BPS Procurement Directive effective April 13, 2026 applies: for goods, an invitational process with at least three suppliers is recommended from $10,000 up to $139,000, and an open competitive process is required at $139,000 or more 8.
Independent and chain operators follow their own policies, often three written quotes for mid-sized orders and a formal RFQ for multi-home rollouts. A written specification makes quotes comparable. See our sourcing page for how we work with institutions.
9. What to send us for a quote
Send the specification you would give any bidder:
- Units by space: resident rooms, semi-private rooms, lounges and dining, outbreak reserve.
- Room dimensions and ceiling heights, or minimum smoke CADR per unit.
- True HEPA (99.97% at 0.3 µm) or MERV 13 minimum; no ozone, UV or ionizer.
- Required approval mark on the finished unit (CSA, ULC, UL, ETL or another ESA-recognized mark).
- Noise ceiling at the overnight setting, if you have one.
- Spare filters per unit and the period they cover.
- Labelling: bilingual labels, asset tags.
- Delivery address(es), date needed on site, and your quote process.
Request a quote with these details, or read our sourcing page to see how we work with long-term care homes.
Institutional supply
Supplying a school, office or facility?
We source and supply first aid kits, safety signage, air purifiers and facility products for Ontario institutions, quoted delivered in Canadian dollars. See institutional supply.
Request a quoteBuying regularly?
Open a wholesale account
Trade pricing, the full product catalogue and live status on every request and order.
Apply to buyCommon questions
Do Ontario long-term care homes have to use HEPA air purifiers?
No. O. Reg. 246/22 does not require portable air cleaners. It does require mechanical ventilation to function at all times and HVAC systems to be inspected at least every six months 5. Public Health Ontario's IPAC checklist treats portable air cleaners as a way to filter indoor air, especially where ventilation options are limited 6.
What size air purifier do I need for a resident room?
Health Canada's rule is that the tobacco smoke CADR should be at least two-thirds of the room's floor area in square feet, assuming an 8-foot ceiling 3. A 168 sq ft private room therefore needs a smoke CADR of at least 112. That delivers about 5 air changes per hour using AHAM's formula, ACH = CADR × 60 ÷ volume 4.
How many air changes per hour should a long-term care lounge get?
None of the federal or Ontario guidance cited here sets a mandatory ACH target for portable units in long-term care. AHAM's suggested room size corresponds to about 4.8 air changes per hour, which is a reasonable planning baseline 4. For a large lounge, PHO recommends using multiple units rather than one 2.
Are ionizer or UV air purifiers acceptable in long-term care?
Public health guidance says to avoid them. Public Health Ontario notes that ozone-generating, UV and ion-generator units may pose health hazards and add little cleaning benefit, and it recommends mechanical filtration only 2. PHAC specifically says ozone-producing air cleaners should be avoided in long-term care homes 1.
What certification mark does an air purifier need in Ontario?
The Electrical Safety Authority says an electrical product must be approved by an accredited certification or evaluation agency, and must carry its mark, before it is used or sold in Ontario 7. Recognized marks include CSA, ULC, UL, Intertek (ETL) and QPS. A component-only mark does not qualify a complete product 7.
How often should HEPA filters be replaced in a care home?
Sources
Every figure and rule above comes from one of these. Where this article draws a conclusion the source does not state literally, or gives an estimate rather than a published number, it says so in the text.
- Public Health Agency of Canada — Using ventilation and filtration to reduce aerosol transmission of COVID-19 in long-term care homes
- Public Health Ontario — Use of Portable Air Cleaners and Transmission of COVID-19 (1st revision, July 2022)
- Health Canada — Choosing a portable air purifier
- AHAM — Portable Air Cleaners and Air Changes per Hour (white paper)
- Ontario e-Laws — O. Reg. 246/22: General, Fixing Long-Term Care Act, 2021
- Public Health Ontario — IPAC Checklist for Long-Term Care and Retirement Homes (2nd revision, March 2025)
- Electrical Safety Authority — Recognized approval marks
- Government of Ontario — Broader Public Sector Procurement Directive (effective April 13, 2026)
- Ontario e-Laws — Broader Public Sector Accountability Act, 2010
Last reviewed November 22, 2026. Rules and rates change. If you find something here that has gone out of date, tell us and we will fix it. This guide is general information, not legal or customs advice.