Facilities & safety

Eyewash station requirements in Ontario: what Reg. 851 says, the ANSI Z358.1 numbers, and how to buy the right unit

Ontario law tells employers to provide eye wash facilities and emergency showers where chemicals can injure eyes or skin. The practical specs come from ANSI Z358.1. Here is how the two fit together for labs, custodial rooms and shops.

Updated November 18, 2026Reading time about 8 minWritten for Facilities managers, health and safety leads, science department heads and purchasing officers at Ontario schools, colleges, municipalities, hospitals and care homes.

The short version

  1. Ontario law sets the duty, not the specs. Section 124 of Reg. 851 requires eye wash facilities, emergency showers or flushing fluids "as are needed" wherever a hazardous chemical or biological agent could injure the eye or skin 2.
  2. ANSI Z358.1 is the yardstick Ontario institutions use. CCOHS summarizes it as at least 1.5 L/min to both eyes for 15 minutes, tepid water between 16 and 38°C, and a unit reachable within 10 seconds 1.
  3. Your buying decision is plumbed, self-contained or bottle. Plumbed or self-contained units are the primary station; personal bottles only supplement them and cannot flush both eyes for 15 minutes 14.
  4. Weekly activation and annual inspection are the norm. CCOHS calls for weekly activation with a signed, dated record and a full inspection every year 1.

Every claim below links to the source it comes from. Where a figure is an estimate rather than a published number, this article says so.

Eyewash station requirements in Ontario start with one short section of Reg. 851, which tells employers to provide eye wash facilities, emergency showers or flushing fluids wherever a hazardous chemical or biological agent could injure the eye or skin. It does not say how much water, how warm, or how far away. Ontario universities, municipalities and school boards fill that gap with ANSI/ISEA Z358.1. This guide puts both in one place, with a worked lab example, an inspection checklist and a procurement spec.

Part one — What the rules require

1. What Ontario law says about eyewash stations

Section 124 of Reg. 851 (Industrial Establishments) applies where a worker is required to work with, or is likely to be exposed to, a hazardous biological or chemical agent that could injure the eye or skin. The employer must provide as many of the following as are needed: eye wash facilities, emergency showers, and antidotes, flushing fluids or washes 2.

Subsection (2) requires the equipment to be clearly signed, in a conspicuous place near where the agent is kept or used, readily accessible, and with use instructions displayed on or near it 2.

Older procedures cite section 125 for deluge showers; it was revoked by O. Reg. 186/19, so showers now sit in section 124 2.

What the regulation does not say

Section 124 contains no flow rate, temperature, mounting height or travel distance 2. CCOHS notes there is no Canadian standard for the design or placement of this equipment and points employers to ANSI Z358.1-2014 (R2020) as a guide 1. The City of Toronto's policy cites section 124 and requires units installed to the current ANSI standard 4.

2. How WHMIS and the SDS tell you where you need one

Section 124 is triggered by the hazard, so start with your chemical inventory. Under WHMIS, every safety data sheet follows the 16 sections listed in Schedule 1 of the Hazardous Products Regulations. Section 4 gives first-aid measures by route of exposure, including eye contact, and Section 8 covers exposure controls and personal protection 3.

The City of Toronto has supervisors review current safety data sheets in a hazard assessment, then select the unit type 4.

Typical Ontario locations that need an eyewash station

  • School and college science labs using acids, bases and stains.
  • Custodial rooms where concentrated cleaners and disinfectants are diluted or decanted.
  • Maintenance and mechanical shops handling battery acid, boiler treatment or solvents.
  • Hospital, lab and care-home utility rooms where biological agents and high-level disinfectants are used.

Hastings and Prince Edward District School Board's Procedure 268 requires principals to ensure an eye wash station and procedure where applicable, with a weekly flush schedule posted 7.

3. ANSI Z358.1 key specs for eyewash station requirements in Ontario

Figures as summarized by CCOHS from ANSI Z358.1-2014 (R2020) 1. Confirm against the current edition before you tender.

RequirementEyewashEye/face washEmergency shower
Minimum flow1.5 L/min (0.4 gal/min) to both eyes 111.4 L/min (3.0 gal/min) 175.7 L/min (20 gal/min) 1
Duration15 minutes 115 minutes 115 minutes 1
ActivationUnder 1 second, hands-free 1Under 1 second, hands-free 1Under 1 second, stays on without hand pressure 5
Water temperatureTepid, 16–38°C 1Tepid, 16–38°C 1Tepid, 16–38°C 1
Height83.8–134.6 cm from floor 183.8–134.6 cm from floor 1Head 208.3–243.8 cm; valve no higher than 173.3 cm 1
ClearanceAt least 15.3 cm from wall 1At least 15.3 cm from wall 186.4 cm unobstructed enclosure 1

The 10-second rule

ANSI recommends that a worker reach the equipment within 10 seconds. CCOHS notes an average person walks 16 to 17 m in 10 seconds, but that figure does not account for someone who has just been injured 1. Waterloo and the University of Toronto require the unit on the same level as the hazard with an unobstructed path; U of T allows one unlocked door that swings in the direction of travel, and recommends no more than 3 m for strong acids and caustics 56.

Why tepid matters

CCOHS notes indoor plumbed systems in cold climates have been measured at 2 to 7°C 1. In an Ontario winter, a cold-water-only line usually needs a thermostatic mixing valve.

4. Plumbed vs self-contained vs eyewash bottles

TypeBest fitWatch for
Plumbed eyewash or eye/face washLabs, custodial rooms and shops with a potable water line nearbyTepid supply, a drain or floor sink, weekly flushing of dead legs 6
Self-contained (gravity-fed)Remote areas, portables, rooms without plumbingMust meet the same 15-minute and tepid requirements; check bladder or fluid expiry and replace after use 1
Emergency shower or combination unitAreas where large-body splash is possible, such as bulk chemical decanting75.7 L/min means heavy water volume; plan drainage and keep 1.5 m from outlets 5
Personal eyewash bottleImmediate first rinse on the way to a station; mobile workersSupplement only; cannot replace a plumbed or self-contained unit or flush both eyes at once 1

The City of Toronto treats antidotes, flushing fluids and personal washes as acceptable only as temporary measures for inaccessible areas or mobile workplaces, never as a replacement for a permanent plumbed station where one can be installed, and requires a used unit to be replaced 4. The University of Waterloo does not permit bottles as eye washes at all, because they cannot hold 1.5 L/min for 15 minutes 6. Bottles go beside the station, not instead of it.

5. Worked example: one secondary school chemistry lab

A secondary school chemistry lab stores dilute acids and bases, and the SDS for each lists eye contact first aid in Section 4 3. Section 124 therefore requires eye wash facilities, clearly signed and near the chemical storage 2. The department chooses one plumbed eye/face wash at the teacher's demonstration bench and one emergency shower by the prep-room door.

  1. Eye/face wash volume: 11.4 L/min × 15 minutes = 171 L per activation 1.
  2. Shower volume: 75.7 L/min × 15 minutes = about 1,136 L per activation 1.
  3. Self-contained alternative: an eyewash-only unit at 1.5 L/min × 15 minutes needs at least 22.5 L of usable fluid 1.
  4. Placement check: walk from the farthest bench to the unit; if it takes more than 10 seconds or crosses a locked door, add a second unit 15.
  5. Temperature check: run the line in January and measure; anything below 16°C means a mixing valve 1.

The shower figure is why drainage belongs in the plan before the purchase order.

Part two — Inspect, specify and buy

6. Get this sourced

Ridgeport Supply Co. sources plumbed and self-contained eyewash stations, eye/face washes, emergency showers, combination units and eyewash signage from overseas manufacturers. We check flow, duration, activation, mounting height and ANSI Z358.1 compliance documentation and test reports against your requirement before you commit, and quote delivered in Canadian dollars. Request a quote and send the product, quantity, specs or standard required, delivery location and date.

7. Eyewash and emergency shower inspection checklist

CCOHS calls for weekly activation by a designated person with a signed, dated record, plus a complete annual inspection 1. Waterloo flushes both hot and cold supplies where there is a mixing valve 6.

  • Unit is marked with a highly visible sign and has use instructions posted on or beside it 25.
  • Path is clear, on the same level as the hazard, and reachable within 10 seconds 16.
  • Dust covers are in place and come off when the unit is activated.
  • Valve opens in under 1 second and stays on hands-free 1.
  • Water reaches both nozzles and runs clear; plumbed units flushed weekly to clear sediment and stagnant water 6.
  • Fluid is tepid, between 16 and 38°C 1.
  • Self-contained units: fluid or bladder within expiry and replaced after any use 1.
  • Tag initialled and dated for the weekly test; annual inspection measures flow and checks for corrosion or damage, and is documented 4.

Toronto also has joint health and safety committee members check stations in monthly inspections 4. See also our guide to Ontario workplace inspection safety supplies.

8. Procurement spec for an eyewash station tender

Write the specification around performance. These lines work in an Ontario RFQ.

  1. Standard: unit certified or tested to ANSI/ISEA Z358.1 (state the edition you accept); supplier to provide the test report or certificate 16.
  2. Type: plumbed eyewash, eye/face wash, shower, combination or self-contained, per location.
  3. Flow and duration: at least 1.5 L/min (eyewash), 11.4 L/min (eye/face wash) or 75.7 L/min (shower) for 15 minutes 1.
  4. Activation: hands-free, open in under 1 second 1.
  5. Tepid water: thermostatic mixing valve delivering 16–38°C where supply is cold 1.
  6. Mounting: heights and clearances to the figures in section 3, plus accessible approach where required.
  7. Included: dust covers, signage, inspection tag, installation instructions and spare parts list.

9. What to send us for a quote

  • Unit type for each location: plumbed eyewash, eye/face wash, shower, combination or self-contained.
  • Quantity by site and room (lab, custodial room, shop, utility room).
  • Standard and edition required, such as ANSI/ISEA Z358.1, and any board or municipal spec.
  • Water supply details: potable line available, cold-only or hot and cold, and whether a mixing valve is needed.
  • Mounting: wall, pedestal or bench-mount, and any accessibility requirement.
  • Accessories: signage, inspection tags, spare covers or replacement fluid.
  • Delivery address in Ontario and the date you need units on site.

Request a quote with these details, or read how Ridgeport sources for institutions first.

Institutional supply

Supplying a school, office or facility?

We source and supply first aid kits, safety signage, air purifiers and facility products for Ontario institutions, quoted delivered in Canadian dollars. See institutional supply.

Request a quote

Buying regularly?

Open a wholesale account

Trade pricing, the full product catalogue and live status on every request and order.

Apply to buy

Common questions

What are the eyewash station requirements in Ontario?

Ontario's eyewash station requirements are in section 124 of Reg. 851. Where a worker works with or is likely to be exposed to a hazardous chemical or biological agent that could injure the eye or skin, the employer must provide eye wash facilities, emergency showers, or antidotes and flushing fluids as needed. The equipment must be signed, conspicuous, near the hazard, readily accessible and have instructions posted 2. Technical specs usually follow ANSI Z358.1 1.

How far can an eyewash station be from a hazard?

Under ANSI Z358.1 as summarized by CCOHS, an eyewash station should be reachable within 10 seconds, which an average person covers in roughly 16 to 17 m 1. The University of Toronto recommends no more than 3 m where strong acids or caustics are used 5.

How often should an eyewash station be tested?

An eyewash station should be activated weekly by a designated person, with a signed and dated record, and fully inspected once a year, according to CCOHS guidance based on ANSI Z358.1 1.

Can eyewash bottles replace an eyewash station?

No. CCOHS states eyewash bottles are a supplement only and cannot replace a plumbed or self-contained eyewash station, because they cannot flush both eyes at once for 15 minutes 1. The City of Toronto allows them only as a temporary measure for inaccessible areas or mobile work 4.

What temperature should eyewash station water be?

Eyewash station water should be tepid, between 16 and 38°C (60 to 100°F), according to CCOHS. Water above 38°C can harm the eyes, and water below 16°C risks hypothermia and shorter rinsing 1.

Sources

Every figure and rule above comes from one of these. Where this article draws a conclusion the source does not state literally, or gives an estimate rather than a published number, it says so in the text.

  1. Emergency Showers and Eyewash Stations — Canadian Centre for Occupational Health and Safety (CCOHS)
  2. R.R.O. 1990, Reg. 851: Industrial Establishments — Government of Ontario e-Laws
  3. WHMIS — Safety Data Sheet (SDS) — CCOHS
  4. Emergency Eyewash and Shower Equipment Policy — City of Toronto
  5. Emergency Eyewash and Shower Standard — University of Toronto Environmental Health and Safety
  6. Eye/Face Washes and Emergency Showers — University of Waterloo Safety Office
  7. Procedure 268: Science Education Safety Grades 9–12 — Hastings and Prince Edward District School Board

Last reviewed November 18, 2026. Rules and rates change. If you find something here that has gone out of date, tell us and we will fix it. This guide is general information, not legal or customs advice.